Data Sheet for Application

Application Sheet
CEN001
Central function weather station
DXR2..18-101A
DXR2..18-102A
3 / 4
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-01
A6V10662238_en--_d_--_05
Application
configuration
Equipment
Values/range
Template settings
On-board input
Outside air temperature
None
X1; LG-Ni1000
X2; LG-Ni1000
X1; 0…10 V
X2; 0…10 V
X1; NTC 100k
X2; NTC 100k
X1; NTC 10k
X2; NTC 10k
X1; T1 (PTC)
X2; T1 (PTC)
X1; Pt1000 (EU)
X2; Pt1000 (EU
X1; Pt1000 (NA)
X2; Pt1000 (NA)
X1; LG-Ni1000
Optional
configuration
Equipment
Values/range
Template settings
On-board input
Relative outside air humidity
None
X2; 0…10 V
X2; 0…10 V
Atmospheric pressure
None
X3; 0…10 V
X3; 0…10 V
Wind speed
None
X2; 0…10 V
X3; 0…10 V
X4; 0…10 V
X4; 0…10 V
Precipitation detector
None
D2; Normally open
X4; Normally open
D2; Normally open
Central shading
function
Precipitation protection
None
Active
Active
Frost protection
None
Active
Active
Protection function
Switch-on delay 1
None
Active
None
Protection function
Switch-on delay 2
None
Active
None
Protection function
Switch-on delay 3
None
Active
None
Standard values
Parameter
Values/range
Template settings
Central seasonal
compensation
Low outside temperature for heating
-70 °C … 70 °C
25 °C
Low setpoint for heating comfort
-70 °C … 70 °C
22 °C
High outside temperature for heating
-70 °C … 70 °C
31 °C
High setpoint heating comfort
-70 °C … 70 °C
23 °C
Low outside temperature cooling
-70 °C … 70 °C
26 °C
Low setpoint for cooling comfort
-70 °C … 70 °C
24 °C
High outside temperature cooling
-70 °C … 70 °C
32 °C
High cooling setpoint for comfort
-70 °C … 70 °C
26 °C
Wind protection
Switch-on point
0 … 1000 m/s
7 m/s
Switch-on delay protection
0 … 1000 min
0 min
Switch-off point
0 … 1000 m/s
5 m/s
Switch-off delay protection
0 … 1000 min
20 min