Assortment / System Description

Radiator application
Electric radiator application
14
66 | 275 A6V10866237_en--_b_08
Y Output signal TR Room temperature
SpH Effective heating setpoint YH1 1-stage
YH Electric radiator
Figure: Example of radiator application
The DRX2 automation station controls electric radiator valves via Triac or
analog outputs, regardless of available I/Os. Single-stage and modulating
electric radiators are supported. Electric radiators, controlled via an analog
output on the DXR2, can receive an enable via a relay or Triac on the DXR2.
A binary overtemperature (open contact) protection can be connected on the
DXR2 for all versions of the electric radiator application. The application
switches off the radiator at device protection priority if overtemperature
protection is enabled.
Description Name Default value
Enable overtemperature input
0:No
1:Yes
EnOvrTDetIn 0:No
WARNING
Electric heat coils require safety limit thermostat
Improper installation of electric heating coils can result in fire and cause
destruction of life and property.
Install a high temperature cut-out switch on all electric heating elements.
Ensure that all wiring and installation conform to applicable safety codes
and regulations.
Actuators
Safety thermostat