User Manual
Application Sheet CEN001
Central function weather station
DXR2..18-
101A
DXR2..18-
102A
3 / 4
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_c_--_05
Application
configuration
Equipment Values/range Template settings
On-board input Outside air temperature None
X1; LG-Ni1000
X2; LG-Ni1000
X1; 0…10 V
X2; 0…10 V
X1; NTC 100k
X2; NTC 100k
X1; NTC 10k
X2; NTC 10k
X1; T1 (PTC)
X2; T1 (PTC)
X1; Pt1000 (EU)
X2; Pt1000 (EU
X1; Pt1000 (NA)
X2; Pt1000 (NA)
X1; LG-Ni1000
Optional
configuration
Equipment Values/range Template settings
On-board input Relative outside air humidity None
X2; 0…10 V
X2; 0…10 V
Atmospheric pressure None
X3; 0…10 V
X3; 0…10 V
Wind speed None
X2; 0…10 V
X3; 0…10 V
X4; 0…10 V
X4; 0…10 V
Precipitation detector None
D2; Normally open
X4; Normally open
D2; Normally open
Central shading
function
Precipitation protection None
Active
Active
Frost protection None
Active
Active
Protection function
Switch-on delay 1
None
Active
None
Protection function
Switch-on delay 2
None
Active
None
Protection function
Switch-on delay 3
None
Active
None
Standard values
Parameter Values/range Template settings
Central seasonal
compensation
Low outside temperature for heating -70 °C … 70 °C 25 °C
Low setpoint for heating comfort -70 °C … 70 °C 22 °C
High outside temperature for heating -70 °C … 70 °C 31 °C
High setpoint heating comfort -70 °C … 70 °C 23 °C
Low outside temperature cooling -70 °C … 70 °C 26 °C
Low setpoint for cooling comfort -70 °C … 70 °C 24 °C
High outside temperature cooling -70 °C … 70 °C 32 °C
High cooling setpoint for comfort -70 °C … 70 °C 26 °C
Wind protection Switch-on point 0 … 1000 m/s 7 m/s
Switch-on delay protection 0 … 1000 min 0 min
Switch-off point 0 … 1000 m/s 5 m/s
Switch-off delay protection 0 … 1000 min 20 min