Application Sheet CEN003
Central function HVAC supply, lighting and blinds operation
DXR2..18-
101A
DXR2..18-
102A
3 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_c_--_07
Description of
functions
Basic function Options
2 x coordination of supply and demand signals for
chilled water
o Setpoint determination for cooling request
o Free cooling
o Disable chilled water sequence based on outside
temperature
o Condensation prevention using local condensation
monitors in the rooms
o Centrale valve kick control
o Central override of all cooling valves
2 x coordination of supply and demand signals for hot
water
o Setpoint determination for heating request
o Disable hot water sequence based on outside
temperature
o Centrale valve kick control
o Central override of all heating valves
1 x coordination of supply and demand signals for air
o Activate supply air supply by a minimum number of
rooms with fresh air demand
o Supply air temperature selection
o Relief function for stable operation of air handling
unit
o
Central override of all VAV
4 central groups for controlling room operating mode
via one digital input.
It can be switched between 2 room operating modes
per group.
Room operating mode control can be enabled for each
group on 3 additional groups with a delay on large
buildings.
2 central groups of manual operation of blinds via
KNX PL-Link switch.
Manual blinds operation can be enabled for each
group on 3 additional groups with a delay on large
buildings.
2 central groups of manual operation of blinds via
KNX PL-Link switch.
VAV position selection for AirOptiControl by damper
position, air flow deviation, or setpoint evaluation of air
flow.
Variants
The room operating modes can be commanded on the
DXR2 via a BACnet reference.
Siemens devices Key Device Datasheet Product no. No.
DXR2… Compact room automation station, BACnet/IP, 24 V,
DIN housing, 2 DI, 4 UI, 8 DO Triacs, 4 AO 0…10 V
N9205
N9207
DXR2.E18-101A
DXR2.E18-102A
DXR2.M18-101A
DXR2.M18-102A
1
Optional third-
party device
Key Device No.
R3 I/O pushbutton interface UP 220/31
2)
5WG1 220-2AB31
1
R4 I/O pushbutton interface UP 220/31
2)
5WG1 220-2AB31
1
D3, D4,
D5, D6
Digital contact to control room operating mode
4
2)
Additional documents on www.siemens.com/gamma-td