User Manual

Application Sheet CEN004
Central function emergency
DXR2..18-
101A
DXR2..18-
102A
4 / 4
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_c_--_08
Engineering The ABT Site engineering tool is required to engineer DXR2 automation stations.
See the Siemens Download Center www.siemens.com/bt/download for the latest application configurations and
workflow tutorials.
HVAC emergency function matrix:
Digital contact for HVAC
emergency shut down
(D9)
Digital contact for HVAC
Forced smoke extraction
with exhaust air (D10)
Digital contact for HVAC
Forced pressure build up
with supply air (D11)
Resulting HVAC
emergency function in the
rooms
On Off Off
Emergency shut down of
all rooms connected to
the group with VAV or fan
coil plants
On On Off
Maximum negative
pressure in all rooms
connected to the group
with VAV or fan coil
plants
On Off On
Maximum positive
pressure in all rooms
connected to the group
with VAV or fan coil
plants
On On On
Maximum purge in all
rooms connected to the
group with VAV or fan
coil plants
It is the life safety and security management, and not Desigo room automation, that is responsible for fire
detection and evaluation of the correct HVAC emergency operating modes for a fire section and primary plants.
The configurable Desigo room automation can switch all available luminaires to a specified value at the highest
priority during an emergency. This is not emergency lighting or evacuation route control, but rather is only a
supporting measure during an emergency to supply all rooms with the maximum brightness.
The configurable Desigo room automation does not support emergency lighting control with service and test
functions for decentralized or centralized batteries.
WARNING
Desigo TRA is not approved by fire authorities.
Fire can result in death or serious injury.
As a consequence, TRA fire solutions are only used on non-critical applications
with a limited risk to health and risks,
For critical application, an individual permit by the fire authorities on site must be
acquired for a specific project.