User Manual

Application Sheet CEN004
Central function emergency
DXR2..18-
101A
DXR2..18-
102A
2 / 4
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_c_--_08
Emergency shading function
CenEmgShd11 Emergency shading function CenEmgShdDly Delays for the emergency shading f
CenEmgDetShd11 Emergency function to read the function
digital commands Shd11 Shading control in the rooms
Description of
functions
Basic function Options
An HVAC emergency shut down can be triggered
during an emergency over a digital command for a
maximum of 2 supply groups. The commands are
executed at the highest priority and cannot be locally
overridden in the room or from another central
operation.
The applicable electrical or mechanical installation can
only be manually or automatically operated after this
digital command is reset.
The HVAC emergency shut down can be tested via a
test function.
During an emergency, additional digital commands
can:
o generate HVAC negative pressure in the rooms.
This can support smoke extraction.
o generate HVAC positive pressure in the rooms.
This can support smoke extraction.
o generate HVAC purge in the rooms.
This can support smoke extraction.
o switch on all luminaires.
o move all facades to a configurable position.
Facade control can be enabled on 3 additional
groups with a delay on large buildings.
Variants
A third-
party device can write the digital commands for
emergency forced control of HVAC, lighting, and
blinds via a BACnet reference.
Siemens devices Key Device Datasheet Product no. No.
DXR2… Compact room automation station, BACnet/IP, 24 V,
DIN housing, 2 DI, 4 UI, 8 DO Triacs, 4 AO 0…10 V
N9205
N9207
DXR2.E18-101A
DXR2.E18-102A
DXR2.M18-101A
DXR2.M18-102A
1
Third-party
devices
Key Device No.
D9 Digital contact for HVAC forced emergency shut down supply air
1
Optional third-
party device
Key Device No.
D7 Digital contact for forced emergency positioning for shading
1
D8 Digital contact for forced emergency positioning command for lighting
1
D10 Digital contact for HVAC forced smoke extraction (exhaust air)
1
D11 Digital contact for HVAC forced pressure build up (supply air) 1