Data Sheet for Application

Application Sheet
HP001
Heat pump, variable fan, reversing valve, 2-stage electric heating,
1-stage electric radiator and outside air damper
DXR2..18-102A
6 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662238_en--_c_--_11
Default values
Parameter
Values/Range
Template settings
Temperature control for
cooling
Fan Operation
Series, Parallel
Series
Temperature control for
heating
Fan Operation
Series, Parallel
Series
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Heating setpoint for Comfort
0 … 50 °C
21 °C
Delta heating setpoint for Pre-comfort
0 … 10 K
1 K
Heating setpoint for Economy
0 … 50 °C
15 °C
Heating setpoint for Protection
0 … 50 °C
12 °C
HVAC
Enable condensate level monitor
Yes, No
Yes
Heating cooling coil
Enable fault input
Yes, No
Yes
Heat pump power
Calculated, Measured
Measured
Engineering
ABT Site engineering tool is required to configure the DXR2 automation stations.
See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
Option combination according to available on-board I/Os on controller.
Management
station
Sample presentation of a heat pump application on the Desigo CC management station.
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
© 2017 Siemens Switzerland Ltd
Subject to change