Data Sheet for Application
Application Sheet
HP001
Heat pump, variable fan, reversing valve, 2-stage electric heating,
1-stage electric radiator and outside air damper
DXR2..18-102A
6 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662238_en--_c_--_11
Default values
Parameter
Values/Range
Template settings
Temperature control for
cooling
Fan Operation
Series, Parallel
Series
Temperature control for
heating
Fan Operation
Series, Parallel
Series
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Heating setpoint for Comfort
0 … 50 °C
21 °C
Delta heating setpoint for Pre-comfort
0 … 10 K
1 K
Heating setpoint for Economy
0 … 50 °C
15 °C
Heating setpoint for Protection
0 … 50 °C
12 °C
HVAC
Enable condensate level monitor
Yes, No
Yes
Heating cooling coil
Enable fault input
Yes, No
Yes
Heat pump power
Calculated, Measured
Measured
Engineering
• ABT Site engineering tool is required to configure the DXR2 automation stations.
• See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
• Option combination according to available on-board I/Os on controller.
Management
station
Sample presentation of a heat pump application on the Desigo CC management station.
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
© 2017 Siemens Switzerland Ltd
Subject to change