User Manual
Application Sheet HP001
Heat pump, variable fan, reversing valve, 2-stage electric heating,
1-stage electric radiator and outside air damper
DXR2..18-102
A
6 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_b_--_11
Default values
Parameter Values/Range Template settings
Temperature control for
cooling
Fan Operation Series, Parallel Series
Temperature control for
heating
Fan Operation Series, Parallel Series
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
HVAC Enable condensate level monitor Yes, No Yes
Heating cooling coil Enable fault input Yes, No Yes
Heat pump power Calculated, Measured Measured
Engineering ∂ ABT Site engineering tool is required to configure the DXR2 automation stations.
∂ See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
∂ Option combination according to available on-board I/Os on controller.
Management
station
Sample presentation of a heat pump application on the Desigo CC management station.