Application Sheet HP001
Heat pump, variable fan, reversing valve, 2-stage electric heating,
1-stage electric radiator and outside air damper
DXR2..18-102
A
6 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662238_en--_b_--_11
Default values
Parameter Values/Range Template settings
Temperature control for
cooling
Fan Operation Series, Parallel Series
Temperature control for
heating
Fan Operation Series, Parallel Series
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
HVAC Enable condensate level monitor Yes, No Yes
Heating cooling coil Enable fault input Yes, No Yes
Heat pump power Calculated, Measured Measured
Engineering ABT Site engineering tool is required to configure the DXR2 automation stations.
See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
Option combination according to available on-board I/Os on controller.
Management
station
Sample presentation of a heat pump application on the Desigo CC management station.