Data Sheet for Application
Table Of Contents
Application sheet VAV282
6 | 11 A6V12189450_en--_a
Application configuration
Group Equipment Values/range Template settings
On-board output Variable air volume
Supply air
Y1, Y2; 3-position
Y10; Y30; 0...10 V
Setpoint for air volume flow; Y10, Y30; 0...10 V
Y10; 0...10 V
Variable air volume
Extract air
Y3, Y4; 3-position
Y20; Y40; 0...10 V
Setpoint for air volume flow; Y20, Y40 0...10 V
Y20; 0...10 V
On-board input Extract air differential
pressure
X1; X3; 0…10V, 4...20mA; SCOM P1; P3; SCOM
Supply air differential
pressure
X2; X4; 0…10 V, 4...20mA; SCOM P2; P4; SCOM
KNX PL-Link devices Room operator unit 1 QMX3.P02, QMX3.P34, QMX3.P36, QMX3.P37,
QMX3.P74
QMX3.P34
Optional configuration
Group Equipment Values/range Template settings
On-board output Cooling coil valve Water; Y1/Y2; Y3/Y4; 3-position
Water; Y1; Y3; pulse width modulation thermal
Water; Y1; Y3; pulse width modulation spring return
Water; Y10; Y20; Y30; Y40; 0...10 V
Water; Y1, Y2; 3-position
Heating/cooling valve 4-pipe, 6-way; Y10; Y20; Y30, Y40; 0..10 V
4-pipe; Y1, Y2, Y3, Y4; pulse width modulation
thermal
4-pipe; Y1, Y2, Y3, Y4; pulse width modulation spring
return
4-pipe; Y10; Y20; Y30, Y40; 0...10 V
Heating coil valve Water; Y1/Y2; Y3/Y4; 3-position
Water; Y1; Y3; pulse width modulation thermal
Water; Y1; Y3; pulse width modulation spring return
Water; Y10; Y20; Y30; Y40; 0...10 V
Electric 1-stage; Y1; Y3; NC
Electric 2-stage; Y1, Y2 or Y3, Y4; NC
Electric modulating; Y1; Y3; pulse width modulation
constant period
Electric modulating; Y10; Y20; Y30, Y40; 0..10 V
Enable electric heating coil Y1; Y3 NC
Ceiling heating/chilled ceiling
valve 1...2
Cooling; Y1/Y2; Y3/Y4; 3-position
Cooling; Y1; Y3; pulse width modulation thermal
Cooing; Y1; Y3; Pulse width modulation spring return
Cooling; Y10; Y20; Y30; Y40; 0...10 V
Heating/chilled 2-pipe; Y1, Y2; 3-position
Heating/cooling 2-pipe; Y1; Y3; Pulse width
modulation thermal
Heating/cooling 2-pipe; Y1; Y3; Pulse width
modulation spring
Heating/cooling 2-pipe; Y10; Y20; Y30; Y40; 0...10 V
Heating/cooling 4-pipe 6-way; Y10; Y20; Y30; Y40;
0...10 V
Water; Y1/Y2; Y3/Y4; 3-position
Heating; Y1; Y3; Pulse width modulation thermal
Heating; Y1; Y3; Pulse width modulation spring return
Heating; Y10; Y20; Y30; Y40; 0...10 V
Chilled ceiling active: Y10; Y20; Y30; Y40; 0...10 V
Chilled ceiling active; Y1/Y2; Y3/Y4; 3-position
Ceiling heating/chilled ceiling passive; Y1; Y3; Pulse
width modulation thermal
Ceiling heating/chilled ceiling passive; Y1; Y3; Pulse
width modulation spring return
Ceiling heating/chilled ceiling passive 2-pipe; Y10;
Y20; Y30; Y40; 0...10 V
Ceiling heating/chilled ceiling passive 4-pipe 6-way;