Assortment / System Description

Lighti
ng applications
Constant lighting control with multiple lighting groups in the room
22
A6V10866237_en--_b_08 229 | 275
Multiple lighting groups control in the room:
The parameters luminance, correction factor daylight, and correction factor
artificial light must be determined by the corresponding brightness
measurement in the room and saved to the automation station to ensure
daylight-dependent lighting in the room is operating properly.
The room occupancy has the following commands available to manually
operate lighting:
Switch on
Switch off
Dimming up
Dimming down
The presence button is used to establish occupancy in a room. It is used in
place of a presence detector. Establishing occupancy with a presence button is
not automatic, but rather the result of a user action. When entering the room,
the user switches to occupied using a presence button. When exiting the room,
the user switches to "absent" using the presence button.
Manual operation by the user can override any existing automation in the room.
Any manual operation must be released to return to automatic mode.
DXR2 applications have the following methods to this end:
A central scheduler program
Presence detector detecting non-occupancy
Central commands from the management station
By manual operation (first-time switch on or appropriately configured
button)
Description Name Default value
Enable brightness control by switch-on command
0:No
1:Yes
EnBrgtCtlSwiOn 1:Yes
Influence of daylight
and artificial light
Manual operation using
the presence button
Manual operation
overrides automatic