Data Sheet for Application
Table Of Contents
Application sheet VVS274
4 | 7 A6V12189448_en--_a
Connection diagram
Application configuration
Group Equipment Values/range Template settings
On-board output Exhaust air VAV position Y10; 0...10 V
Y1, Y2
Y10, 0..10V
Fume hood stabilizing jet Y10, Y20; Y30; Y40, 0...10 V Y20
On-board input Extract air differential pressure X1; 0..10V, 4..20mA; SCOM SCOM
Fume hood sash position 1 B1; B2; 0..10kOhm B1
Fume hood face velocity X1; X2; X3; X4; 0..10V X2
Fume hood state stabilizing jet
fan monitoring
D1; D2; D3; X1; X2; X3; X4; NC
(normally closed)
D1
KNX PL-Link devices Operator display panel QMX3.P87, QMX3.P88 QMX3.P88
Lighting RL512/23, RS510/23, UP510/03,
UP510/23, RS525/23, UP525/13,
JB512C23, JB510C23,
JB525C23
RS510/23
Optional configuration
Group Equipment Values/range Template settings
On-board output Fume hood alarm contact Y1; Y2; Y3; Y4; NC
Fume hood decommissioning
contact
Y1; Y2; Y3; Y4; NC
Binary output 1...4 Y1; Y2; Y3; Y4; NC
Analog output 1...4 Y10; Y20; Y30; Y40; 0...10 V
On-board input Exhaust air VAV air velocity X1; 0...10V
Extract air temperature X1; X2; X3; X4: LG-Ni1000,
0...10V; NTC100k, NTC 10k, T1
(PTC); Pt1000 (EU, NA);
4...20mA
Fume hood sash position 2 B1; B2; 0...10kOhm