Application sheet VVS274
A6V12189448_en--_a 1 | 7
Application sheet VVS274
Fume hood with variable air volume flow control, stabilizing jet, vertical and horizontal
sash with lighting
● Fume hood exhaust air volume control and control for fast, precise VAV actuator on 0...10V output.
● Consisting of functions for face velocity setpoint, exhaust air volume flow setpoint, sash positioning, and lab
operator display panel. Integrated lighting control
● Control and monitoring of the stabilizing jet fan
● Configure the exact functionality based on connected devices and application block.
● Configurable, generic universal control functions for free I/Os
Plant diagram with integrated lighting control
DXR2… Room automation station
YE VAV exhaust air control with damper actuator YEM and pressure sensor YEP
SV Vertical sash sensor
RU Fume hood control unit
F Flow sensor
L Lighting
SJ
DS
Fan for stabilizing jet
State of stabilizing jet
R Room