Data Sheet for Application

Table Of Contents
Application sheet VAV285
A6V12189441_en--_a 3 | 11
Function description
Basic functions
PID control for volume flow control of supply and
exhaust air, room pressurization with room air
pressure sensor, temperature and air quality
The following priority prevails if functions conflict:
1. Room pressure control, 2. Air change rate, 3.
Temperature control.
Alarms for room pressurization and ventilation
Room pressurization with door contact to freeze
room pressure control loop
The room operator unit measures temperature,
humidity, and air quality (CO2).
The application allows customers to adjust the
room temperature setpoints and rapid ventilation
via the room operator unit
Display of room air quality on room operator unit
The operating modes are Comfort, Pre-Comfort,
Economy and Protection
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured
Supports VAV damper actuators for supply and
exhaust air 0…10 V.
Regular automatic pressure sensor calibration
(DXA.S04P…)
Options
Exhaust VAV actuator 0…10 V
PID control LTHW radiator heating
Heating and cooling coils with 3-position valves
controlled via triac outputs
Control for supply air humidification
Downdraft compensation
Outside temperature (for downdraft compensation)
distributed over BACnet
Optimal energy efficiency by including the option
for room/supply air cascade control, presence
detector or window contact
Optional system alarms displayed on the
management station notify building operators of
possible faults
Optional trends can be activated for room sensors
Auxiliary functions
Rapid ventilation
Air volume flow tracking for positive and negative
room air pressure
Supply air functions to coordinate demand signals
for pressure optimized fan control
Green Leaf function (energy saving indication)
Multisegment use of DXR2 automation stations
with VAV application
Control via central commands (e.g. scheduler for
room operating mode)
Central optimum start control provides best room
comfort at the start of occupancy
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit
Central override functions for valves
Emergency function with maximum air change rate
at a constant pressure
Seasonal compensation of room temperature
setpoints
Configurable, generic universal control functions
for free I/Os
Variants
PWM constant (including spring return) or PWM
thermal control can be selected for valves
Room operator unit and sensor variants:
KNX PL-Link wall-mount sensor
KNX PL-Link flush-mount room operator unit
KNX PL-Link flush-mount sensors
Analog exhaust air temperature sensor
KNX PL-Link sensor or binary sensor detects
presence