Data Sheet for Application

Table Of Contents
Application sheet VAV284
8 | 11 A6V12189438_en--_a
Group Equipment Values/range Template settings
Heating coil overtemperature
detector
D1; D2; D3; NO
X1; X2; X3; X4; NO
Radiator overtemperature
detector
D1; D2; D3; NO
X1; X2; X3; X4; NO
Condensation monitor for
chilled ceiling
D1; D2; D3; NO
X1; X2; X3; X4; NO
Condensation monitor VAV
cooling coil
D1; D2; D3; NO
X1; X2; X3; X4; NO
Humidity detector in duct D1; D2; D3; NO
X1; X2; X3; X4; NO
Flow sensor D1; D2; D3; NO
X1; X2; X3; X4; NO
Blinds collision detector 1..2 D1; D2; D3; NO
X1; X2; X3; X4; NO
Binary input 1..7 D1; D2; D3; NO
X1; X2; X3; X4; NO
Analog output P1; P2; P3; P4; SCOM
X1; X2; X3; X4: LG-Ni1000, 0...10 V; NTC100k, NTC
10k, T1 (PTC); Pt1000 (EU, NA); 4...20mA
Default values
Group Parameter Values/range Template settings
Temperature setpoints Cooling setpoint for Comfort 0...50 °C 24 °C
Delta cooling setpoint for Pre-
comfort
0...10 K 1 K
Cooling setpoint for Economy 0...50 °C 35 °C
Cooling setpoint for Protection 0...50 °C 40 °C
Heating setpoint for Comfort 0...50 °C 21 °C
Delta heating setpoint for Pre-
comfort
0...10 K 1 K
Heating setpoint for Economy 0...50 °C 15 °C
Heating setpoint for Protection 0...50 °C 12 °C
Ventilation control Setpoint room air quality for
Comfort
0...2000 ppm 900 ppm
Setpoint room air quality for Pre-
comfort
0...2000 ppm 1100 ppm
Setpoint room air quality for
Economy
0...2000 ppm 1500 ppm
Setpoint room air quality for
Protection
0...2000 ppm 1500 ppm
Supply air VAV Supply air VAV max. air volume
flow
Cooling
0...10,000 m3/h 100 m3/h
Supply air VAV min. air volume
flow
Cooling
0...10,000 m3/h 50 m3/h
Supply air VAV max. air volume
flow
Heating
0...10,000 m3/h 100 m3/h
Supply air VAV min. air volume
flow
Heating
0...10,000 m3/h 50 m3/h