Commissioning Instructions

Configuration & Setup
Alarm Integration
0
A6V12012974
Restricted
9 | 10
Alarm Integration
The Event Enrollment objects DiffPRAlm and AlmInd handle alarm integration for the Alternate RPM Solution.
DiffPRAlm (Room differential pressure alarm)
AlmInd (Alarm indication)
The typical setup is audible with sound at the panel. This is the default configuration.
To configure for non-default silent setup, do both of the following:
Set DiffPRAlm parameter "Suppress event notification" to No.
Set AlmInd parameter "Enable event detection" to No.
When this is done, the EE object DiffPRAlm will annunciate alarm conditions silently.