Commissioning Instructions
Configuration & Setup
Alarm Integration
0
A6V12012974
Restricted
9 | 10
Alarm Integration
The Event Enrollment objects DiffPRAlm and AlmInd handle alarm integration for the Alternate RPM Solution.
● DiffPRAlm (Room differential pressure alarm)
● AlmInd (Alarm indication)
The typical setup is audible with sound at the panel. This is the default configuration.
To configure for non-default silent setup, do both of the following:
● Set DiffPRAlm parameter "Suppress event notification" to No.
● Set AlmInd parameter "Enable event detection" to No.
When this is done, the EE object DiffPRAlm will annunciate alarm conditions silently.