Commissioning Instructions

Configuration & Setup
Function
0
8 | 10
Restricted
A6V12012974
Parameters Basic Operation Silent Operation Synchronized Operation
Backlight brightness Set as desired Set as desired Set as desired
Backlight timeout
(1)
Set as desired, max = 120min Set as desired, max = 120min Set as desired, max = 120min
Rm DiffP alarm
> Event parameters
(2)
TimeDelay: 0 TimeDelay: >0
Typically based on time needed to
enter or exit the room
TimeDelay: >0
Typically based on time needed to
enter or exit the room
Low limit: as specified Low limit: as specified Low limit: as specified
High limit: as specified High limit: as specified High limit: as specified
Neutral zone: as specified Neutral zone: as specified Neutral zone: as specified
Alarm indication
> Event parameters
TimeDelay: >0
Typically based on time needed to
enter or exit the room
TimeDelay: n/a
Audible alarm is disabled by
setting "Enable event detection" to
No
TimeDelay: 0
Audible alarm trips at the same
time as visual (DiffPRAlm) if this
delay is 0
StateList: DO NOT change StateList: DO NOT change StateList: DO NOT change
Alarm indication
> Enable event detection
Yes No Yes
ODP field 2
> Default command
Set to "Diff.air pressure"
(can be set to "Blank" if desired,
ODP displays blank screen)
Set to "Diff.air pressure"
(can be set to "Blank" if desired,
ODP displays blank screen)
Set to "Diff.air pressure"
(can be set to "Blank" if desired,
ODP displays blank screen)
1)
The backlight turns on whenever the LED changes, and also with user/ODP interaction.
2)
See figure below for how to set High limit and Low limit.
There is no automatic timeout function for a muted alarm. If the Mute button is
pressed to silence an active alarm, the buzzer will remain muted for as long as
the alarm condition exists.
High limit and Low limit (how to set up):
Key
1 In a negative pressure room, the High limit setting is closest to neutral pressure.
2 In a positive pressure room, the Low limit setting is closest to neutral pressure.