Commissioning Instructions
Configuration & Setup
Function
0
A6V12012974
Restricted
7 | 10
Configuration & Setup
Step 1 - In ABT Site, select Pressure monitor from Types in library.
Step 2 - Select room pressure monitor(s) (CET room pressurization for room).
Step 3 - For each room, make choice selections for:
● On-board input
● KNX PL-Link device
● HVAC
When setting up multiple ODPs for multiple isolation rooms, the LED will flash and
the display will show "Close the sash, Failed, Do not use" until all ODPs have
been configured. This is expected.
Step 4 - For each Room ODP, go to Default values in ABT Site.
Step 5 - Set parameters to desired specification, see table.
Basic steps:
1. Determine the pressure level(s) for the alarm.
2. Set pressure level(s) for the alarm, and set the desired delay time.
3. Set the desired delay time for the audible alarm.