Commissioning Instructions
Overview
Function
0
6 | 10
Restricted
A6V12012974
NOTICE
Emergency Max Button – Do Not Use
In the Alternate RPM Solution, the Emergency Max button on the ODP performs
no function. If someone presses it by mistake, the red LED and buzzer respond
for 1 second and then return to normal. Pressurization is not affected.
· Make sure to affix the label “Do Not Use”, found in the product carton, over
the words “Emergency Max”
BAS Alarm Integration
The room pressure monitor can communicate on a BAS network to give the building operation staff the same
information that is available at the ODP.
● Audible setup handled by EE object AlmInd. (typical setup with sound at the panel)
● Silent setup handled by EE object DiffPRAlm. (not default, requires configuration)
See Configuration & Setup > Alarm Integration [➙ 9] for details.