Inputs
The inputs are protected against incorrect wiring AC 24 V.
Inputs: Overview
Type
Inputs
DXR2.E17C… 3 DI, 4 UI, 2 resistive inputs, SCOM
Resistance sensor, analog (inputs X...)
Type
Range (over range)
Resolution
AI 1000 Ohm *) 1 kΩ (0...1.05 kΩ) 10 Ω
Resistance sensor, analog (inputs B...)
Type
Range (over range)
Resolution
AI 10 kOhm *) 10 kΩ (0...10.5 kΩ) 50 Ω
Temperature measurement, analog (inputs R1K...)
Type
Range (over range)
Resolution
AI PT1K 375 *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI PT1K 385 *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI Ni1000 *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI Ni1000 DIN *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI T1 (PTC) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
10 mK
0.18 °F
AI NTC10K
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
10 mK (25 °C)
0.045 °F (77 °F)
AI NTC100K
-40...70 °C (-40...158 °C)
-40...158 °F (-40...316°F)
25 mK (25 °C)
0.045 °F (77 °F)
*) A fixed value of 1 Ω is calibrated to correct line resistance.
Voltage measurement, analog (inputs X...)
Type
Range (over range)
Resolution
AI 0...10 V 0...10 V (-1...11 V) 1 mV
AI 0...10 V standard 0...100% (-10...110%) 1 mV
Open connection: Negative voltage -3.0 V,108 μA (line failure detection)
Current measurement, analog inputs (inputs X...)
Type
Range (over range)
Resolution
AI 120 4...20 mA (-1...11 V) 13 μA
Load resistance
490 / 440 ohms, pulsing (cyclic interrogation of the I/O points)
Note: if the peripheral device can not drive this load, the signal must be
connected via a current measuring converter.
Open connection can be detected. Supports 0…20 mA input range, with signal voltages >10 V. Use AI type U10
instead with an external resistor.