User Manual

8
Siemens Industry, Inc.
A6V10959860_en--_f
Smart Infrastructure
2019-06-28
Technical data
Housing
Color RAL 7035 (light-gray)
Dimensions See Dimensions
Weight
DXR2.E17C..
Terminal cover
Packaging
ca. 350 g
ca. 80 g
ca. 40 g
Function data
Processor Texas Instruments AM3352, 600 MHz
RAM
Flash
512 MB SDRAM (DDR3)
512 MB NAND Flash
A/D and D/A Resolution
Analog inputs X
Analog inputs B (resistance)
Analog Outputs (Y10-Y40)
16 bit
14 bit
10 bit
Power data
Power supply
Operating voltage AC 24 V -15%/+20%
Frequency 50/60 Hz
Power consumption including connected field devices
DXR2.E17C
DXR2.E17CX
Max. 66 VA at AC 24 V
30 data points
60 data points
Internal fuse 4 A irreversible
Transformer with secondary current limitation of max. 10 A or
external secondary current fuse
Non-renewable fuse
Circuit breakers
Max. 10 A, (Class 2, 4A)
Max. 13 A, characteristic B, C, D as per
EN 60898
Apparent power (VA) for transformer design
Base load
including I/O
without load by
field devices
Max. output
load triac at
500 mA each
Max. load for
AC 24 V field
supply at
200 mA
Max. load KNX
PL-Link at
50 mA
Max. load for
DC 24 V field
supply at
100 mA
Power
consumption
including
connected field
devices
DXR2.E17C 8 VA 4 x 12 = 48 5 2 3 66
DXR2.E17CX 8 VA 4 x 12 = 48 5 2 3 66