User Manual

2
Siemens Industry, Inc.
A6V10959860_en--_f
Smart Infrastructure
2019-06-28
Features
Programmable
The DXR2... automation stations provide the infrastructure for system and application-specific
functions and can be programmed.
Compact series
The compact build permits mounting in narrow spaces and on standardized DIN rails, and is
particularly well suited for compact panels or plants with integrated panel.
Plug-in terminal blocks
Plug-in terminal blocks to easily exchange room automation stations.
Use
Desigo Room Automation applications combine multiple disciplines (HVAC for pressurized
rooms and fume hoods, lighting and shading) into one comprehensive solution.
Desigo Room Automation offers the highest level of flexibility for energy-optimized solutions
while satisfying requirements for pressurization, ventilation and comfort using standard tools
and established workflows.
Desigo Room Automation applications can be enhanced with lighting and blinds via KNX PL-
Link.
Preloaded applications
Pressurized rooms and fume hoods
Application works self-contained or distributed across multiple automation stations.
1 room segment control (30 data points)
- operates one supply and one extract terminal or one fume hood, as well as coordinates
operation between multiple room segments.
2 room segment control in single automation station (60 data points)
- operates two supply and two extract terminals or one fume hood, as well as coordinates
operation between multiple room segments.
Variable (VAV) and constant volume flow
with 2-stage electric heating
with hot water
with hot water and flow temperature control
with hot water and thermal power control
Chilled beam active or passive cooling (2-pipe) or cooling/heating (2-pipe) or cooling/heating
(4-pipe)
Radiant ceiling: Cooling, cooling and heating (2-pipe), or cooling/heating (4-pipe)
Radiator: Hot water, steam (2 or 4-pipe) or electric stepped controlled
Light: Up to 4 separate zones
Blinds: 1 or 2 motors
Fume hood
Application options
Separate temperature and volume setpoints for all 4 operating modes.
Supply and extract air flow tracking
Room pressure cascade control
Accepts external demand control ventilation signal
Chilled water and hot water valve