Desigo® Room Automation Room Automation Station, BACnet/IP, AC 24 V DXR2.E17C... For buildings with room pressurization and fume hood control applications, leveraging the functionality and flexibility of Desigo Room Automation applications.
Features Programmable The DXR2... automation stations provide the infrastructure for system and application-specific functions and can be programmed. Compact series The compact build permits mounting in narrow spaces and on standardized DIN rails, and is particularly well suited for compact panels or plants with integrated panel. Plug-in terminal blocks Plug-in terminal blocks to easily exchange room automation stations.
Functions The selected application and its parameters as well as input and output configuration determine the room automation station's functionality. A detailed description of functionality is available in the ABT (Automation Building Tool) online help.
The internal KNX PL-Link supply cannot be operated parallel to external power supplies. The internal KNX PL-Link power must be switched off during the engineering phase for external power. This is typically the case if the 50 mA from the internal supply is not enough to supply all devices connected on the KNX PL-Link bus. Type summary Order numbers Worldwide (without US and Canada) Type Stock number Applications Inputs Outputs DXR2.
Product documentation Topic Title Document ID: Installation, cable length, topology Desigo TRA installation guide CM111043 Engineering and commissioning, workflow ABT online help n/a Commissioning Desigo TRA - Setup and Service Assistant CA111050 Product environmental declaration Product environmental declaration CM1E9205 Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.
DC 0…10 V outputs The DC 0…10 V outputs supply max. 1 mA. AC 24 V supply for field devices (V~) Actuators (valves, dampers) and active sensors are supplied directly by the device. Separate AC 24 V power supply is only required if field devices consume more than 5 VA. DC 24 V power supply for field devices (V+) Actuators (valves, dampers) and active sensors are supplied directly by the device. A separate DC 24 V field supply is only required if field devices use more than 2.4 W.
9205J01 Terminal cover Break off the cable inlets to insert the cables to the room automation station. To take off the terminal cover: Operation The outputs have no electricity when power fails. USB communications that does not work points to improper grounding of AC 24 V operating voltage (connection ⏊ must be grounded). Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.
Technical data Housing Color RAL 7035 (light-gray) Dimensions See Dimensions Weight DXR2.E17C.. Terminal cover Packaging ca. 350 g ca. 80 g ca.
Inputs The inputs are protected against incorrect wiring AC 24 V. Inputs: Overview Type Inputs DXR2.E17C… 3 DI, 4 UI, 2 resistive inputs, SCOM Resistance sensor, analog (inputs X...) Type Range (over range) Resolution AI 1000 Ohm *) 1 kΩ (0...1.05 kΩ) 10 Ω Type Range (over range) Resolution AI 10 kOhm *) 10 kΩ (0...10.5 kΩ) 50 Ω Resistance sensor, analog (inputs B...) Temperature measurement, analog (inputs R1K...) Type Range (over range) Resolution AI PT1K 375 *) -40...70 °C (-45...
Digital input (inputs X...) Contact query voltage Universal input: 18 V Digital input: 21 V Contact query current Universal input: 1.2 mA; 7.4 mA initial current Digital input: 1.6 mA; 9.4 mA initial current Contact resistance for closed contacts Max. 100 Ω Contact resistance for open contacts Min. 50 kΩ Outputs The outputs are protected against short circuiting and incorrect wiring AC 24 V. Outputs: Overview Type Outputs DXR2.E17C… 4 triacs, 4 AO Analog (outputs Y10...
Connections Interfaces Ethernet Plugs: 2 x RJ45, screened Interface type: 10Base-T/100BASE-TX, IEEE 802.3 compatible Bitrates: 10/100 Mbps, autosensing Protocol: BACnet over UDP/IP USB (2.0) Plug: Type B Data rate: 12 Mbps KNX Type: KNX TP1 PL-Link, galvanic isolation Baud rate: 9.6 kbps Bus power: 50 mA Short-circuit proof protection against faulty wiring at max. AC 24 V SCOM Interface type: RS485 Baud rate: 115200 Short-circuit proof protection against faulty wiring at max.
Ambient conditions and protection classification Climatic ambient conditions ● Transport (packaged for transport) as per IEC EN 60721-3-2 ● ● ● Operation as per IEC/EN 60721-3-3 Class 2K3 Temperature -25...70 °C (-13... 158 °F) Air humidity 5...95% (non-condensing) Class 3K5 Temperature -5...45 °C (23... 113 °F)/ -5...50 °C (23... 122 F) See Mounting Air humidity 5...
Connection terminals DXR2.E17C and DXR2.E17CX Pin Description 1, 2 Ethernet 2 x RJ45 interface for 2-port Ethernet switch 11, 12 KNX KNX connection +, - 31...41 inputs 10K Resistance input Universal input System neutral ⏊ Field supply AC 24 V for active sensors V~ Field supply DC 24 V for active sensors V+ Module Channel B1, B2 1 9…10 X1...X4 1 5…8 1 1…3 11 1…4 21 1…4 USB USB interface 51...52 power 24V~ Power supply SELV / PELV AC 24 V System neutral ⏊ 61...
Dimensions Issued by Siemens Industry, Inc. Smart Infrastructure 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 14 Siemens Industry, Inc. Smart Infrastructure Document ID A6V10959860_en--_f Edition 2019-06-28 © Siemens Industry, Inc., 2019 Technical specifications and availability subject to change without notice.