Data Sheet for Product

10
A6V10959860_en
2021-06-16
Inputs
The inputs are protected against incorrect wiring AC 24 V.
Inputs: Overview
Type
Inputs
DXR2.X17C… 3 DI, 4 UI, 2 resistive inputs, SCOM
Resistance sensor, analog (inputs X...)
Type Range (over range) Resolution
AI 1000 Ohm *) 1 kΩ (0...1.05 kΩ) 10 Ω
Resistance sensor, analog (inputs B...)
Type Range (over range) Resolution
AI 10 kOhm *) 10 kΩ (0...10.5 kΩ) 50 Ω
Temperature measurement, analog (inputs R1K...)
Type Range (over range) Resolution
AI PT1K 375 *) -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI PT1K 385 *) -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI Ni1000 *) -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI Ni1000 DIN *) -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
25 mK
0.045 °F
AI T1 (PTC) *) -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
10 mK
0.18 °F
AI NTC10K -40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
10 mK (25 °C)
0.045 °F (77 °F)
AI NTC100K -40...70 °C (-40...158 °C)
-40...158 °F (-40...316°F)
25 mK (25 °C)
0.045 °F (77 °F)
*) A fixed value of 1 Ω is calibrated to correct line resistance.
Voltage measurement, analog (inputs X...)
Type
Range (over range)
Resolution
AI 0...10 V 0...10 V (-1...11 V) 1 mV
AI 0...10 V standard 0...100% (-10...110%) 1 mV
Open connection: Negative voltage -3.0 V,108 μA (line failure detection)