Application

Point Database
72
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
76
OCC SEN EVAL
BCalcVal
6
RPscDet
Room presence
detection
Absent
--
--
Present
Absent
77
WINDOW EVAL
BCalcVal
7
RWndSta
Room window state
Closed
--
--
Opened
Closed
78
FRE CLGREQ 1
BCalcVal
275
FreeCReq
Free cooling request
Inactive
--
--
Active
Inactive
79
SU FLO1SAT
BCalcVal
357
VavSuAflStr
tn1
Supply air VAV air
vol.flow saturation 1
Satisfd
--
--
Starved
Satisfd
80
SU FLO2SAT
BCalcVal
358
VavSuAflStr
tn2
Supply air VAV air
vol.flow saturation 2
Satisfd
--
--
Starved
Satisfd
81
SU FAN1CST
BCalcVal
362
FanSuCstV
al1
Coasting value of supply
air fan 1
Off
--
--
On
Off
82
SU FAN2CST
BCalcVal
363
FanSuCstV
al2
Coasting value of supply
air fan 2
Off
--
--
On
Off
83
AIR VOL1RF
BPrcVal
364
VavSuAirFl
Rlf1
Supply air VAV air
volume flow relief 1
Off
--
--
On
Off
84
AIR VOL2RF
BPrcVal
365
VavSuAirFl
Rlf2
Supply air VAV air
volume flow relief 2
Off
--
--
On
Off
85
CND MSG RS
BCalcVal
366
CdnMsgRs
Result of condensation
message
Inactive
--
--
Active
Inactive
86
DEV STATUS
CmnEvt
0
AsSta
Automation station state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
87
IO STATUS
CmnEvt
2
IOBusSta
I/O bus state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
88
PLNK STATUS
CmnEvt
4
PlnkBusSta
KNX PL-Link bus state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
89
RM STATUS
CmnEvt
12
RSta
Room state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
90
SEGM STATUS
CmnEvt
13
RSegmSta
Room segment state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
91
RM OP MODE
MPrcVal
17
ROpMod
Room operating mode
Protect
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
92
GREEN LEAF
MPrcVal
19
REei
Energy efficiency
indication room
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--