Application

Room Segment Functions
Device Control Functions HVAC
56
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure Building Products
2019-04-01
Parameters
Description
Parameter
Pre-loaded Value
Switch-on point for differential pressure (1 and 2)
SwiOnPtDiffP
4%
Hysteresis for differential pressure (1 and 2)
HysDiffP
2%
Setpoint selector for extract air VAV box (1 and 2)
SpSelVavEx
Supply airflow
Switch-on point for air volume flow state (1 and 2)
SwiOnAirFlSta
4%
Hysteresis for air volume flow state (1 and 2)
HysAirFlSta
2%
Enable monitoring for fan state → Must = 0:No for parallel fan
powered box applications; must = 1:Yes for series fan powered box
applications.
EnMonFanSta
No
Enable monitoring for missing air volume flow
0:No
1:Yes
EnMonNoAirFl
Yes
Minimum Ventilation Flow
In all installations (with or without demand control ventilation DCV), the Room
ventilation function provides minimum primary airflow when configured ventilation
is required. This can be set and enabled per operating mode. This provides
additional flexibility and energy savings and effectively replaces the VAV minimum
cooling and heating supply airflow setpoints. During heating (or cooling) when a
minimum heating (or cooling) flow setpoint is configured, the larger value
compared to ventilation will be used.
NOTE:
VAV and FPB have the minimum room air volume flow for the room operating
modes configured and enabled in the VAV Ventilation Control application
function, as follows:
- Minimum room air volume flow for comfort 150 CFM
- Min. room air volume flow for pre-comfort 150 CFM
- Minimum room air volume flow for economy 0 CFM
- Min. room air volume flow for protection 0 CFM
The minimum ventilation setting provides a low limit to the terminal box minimum
ventilation parameter (VavSuAflMinVnt), preventing minimum ventilation from
going below 150 CFM. For more information, see Airflow Sequencing and
Airflow Limits (found under Air Volume Flow Setpoint Calculation section).