Commissioning Instructions
Central Functions
Configuring Central Function for Supply Air Temperature Setpoint Evaluation
5
16 | 21
Restricted
A6V12006922
1. The selected set of default value for theSupply chain air for Setpoint for supply air temperature
determination are displaced in the left window
2. Change the default values so they are consistent with energy code recommendations for the VAV
System. For example, Cooling should be from 50 °F to 65 °F.
3. Close the application.
4. Add the Central Function device to the building hierarchy.
1. Choose the Default Values task.