Application
14022 Point Database
81
Siemens Industry, Inc.
Application Note
A6V11692055
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Defaul
t
Value
Units
Enumeration
On
Text
Off
Text
115
VAV MODE
MPrcVal
740
VavSuDev
Mod
Supply air VAV device
mode
Off
--
1:Off
2:CtrlMod
3:MxAiVlFl
4:MnAiVlFl
5:SmCtAFlS
--
--
116
1VAV CHGVR
MPrcVal
741
VavSuChovr
Cnd1
Supply air VAV
changeover condition 1
Neithe
r
--
1:Neither
2:Heating
3:Cooling
4:Neutral
--
--
117
2VAV CHGVR
MPrcVal
742
VavSuChovr
Cnd2
Supply air VAV
changeover condition 2
Neithe
r
--
1:Neither
2:Heating
3:Cooling
4:Neutral
--
--
118
SU AIR1DMD
MCalcVa
l
743
VavSuAirD
md1
Supply air VAV air
demand 1 f.plant mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:Cooldown
8:RmLTProt
9:CdOvrFPr
10:FreeCool
11:NghtCool
12:Vent
13:EqTmpPro
14:ArVlFlwO
15:SmkCPoPr
16:SmkCNgPr
17:Purge
--
--
119
SU AIR2DMD
MCalcVa
l
744
VavSuAirD
md2
Supply air VAV air
demand 2 f.plant mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:Cooldown
8:RmLTProt
9:CdOvrFPr
10:FreeCool
11:NghtCool
12:Vent
13:EqTmpPro
14:ArVlFlwO
15:SmkCPoPr
16:SmkCNgPr
17:Purge
--
--
BACnet Object Types:
⚫ AI, AO, BI, BO, MI, MO – Standard BACnet physical inputs and outputs.
⚫ APrcVal, BPrcVal, MPrcVal – Analog, Binary or Multi-state Process Values are
virtual outputs (not connected to hardware) with priority arrays. They can be
commanded by the application or by external sources.