Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Defaul
t
Value
Units
Enumeration
On
Text
Off
Text
105
PLANT
OPMODE
MPrcVal
23
PltOpMod
Plant operating mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:CoolDown
8:RmLTProt
9:NUsed1
10:FreeCool
11:NghtCool
12:Vent
13:NUsed2
14:AVlFlOf
15:SmCtPoPr
16:SmCtNgPr
17:Purge
--
--
106
DCV IND EVAL
MCalcVa
l
24
RAQualInd
Room air quality
indication
Undef
--
1:Undef
2:Poor
3:Okay
4:Good
--
--
107
HC DEMAND
MCalcVa
l
31
HCDmd
Heating/cooling demand
Neithe
r
--
1:Neither
2:Heating
3:Cooling
--
--
108
RAD HW DMD
MCalcVa
l
34
RadHwDmd
Radiator hot water
demand
Off
--
1:Off
2:HeatDmd
3:Warm-up
--
--
109
RAD DEV
MODE
MPrcVal
35
RadDevMo
d
Radiator device mode
Off
--
1:Off
2:CtrlMode
3:FullOpen
4:CMdDwDrf
5:DwnDrft
--
--
110
PANEL CW
DMD
MCalcVa
l
86
RcgChwDm
d
Radiant ceiling chilled
water demand
Off
--
1:Off
2:CoolDmnd
3:FreeCool
--
--
111
PANEL MODE
MPrcVal
87
RcgDevMod
Radiant ceiling device
mode
Off
--
1:Off
2:CtrlMod
3:FullOpen
--
--
112
HTG DEV
MODE
MPrcVal
94
HclDevMod
Heating coil device mode
Off
--
1:Off
2:CtrlMod
3:FullOpen
--
--
113
RM UNIT STA4
BAPerip
heralDev
ice
393
ROpUn 1
Room operator unit 1
Operat
.
--
1:Operat.
2:DevStopd
3:DevNAsgn
4:DevMisng
5:CnfngDev
6:Unused
7:CnfError
8:Searchng
--
--
114
OP MODE EFF
MCalcVa
l
516
PrOpMod
Present operating mode
Protec
t
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--