Application

Room Segment Functions
Device Control Functions HVAC
69
Siemens Industry, Inc.
A6V11692055
Smart Infrastructure Building Products
2019-04-01
will signal "No" and the next available cooling resource in the temperature control
sequence will be activated.
For cooling available status to be "Yes", device mode must equal "Control mode"
(modulation).
Configuration
Parameters
Description
Name
Default value
Enable condensation monitor input
EnCdnMonIn
Yes
Enable dew point temperature
This should only be enabled if the primary chilled
water temperature is provided to the controller.
EnTDwp
Yes
Min.diff.dew point/chilled water temp.
TDiffDwpChwMin
2 [°F]
1 [°C]
Hys.f.min.diff.dew point/chilled w.temp.
HysTDiffDwpChw
1.5 [°F]
0.9 [°C]
Switch-on point for chilled water demand
SwiOnPtChwDmd
4%
Hysteresis for chilled water demand
HysChwDmd
2%