Application

Room Functions
Room Operating Mode Determination
34
Siemens Industry, Inc.
A6V11692055
Smart Infrastructure Building Products
2019-04-01
Description
Parameter
Default value
Pre-Comfort / Comfort. All impacts to HVAC operation
are considered (such as window contact, presence
detector, manual fan and setpoint adjust).
(c) Manual operation lock
Manual operation lock configuration → During the
indicated room operating modes, manual HVAC
operation is locked and Comfort cannot be increased,
therefore energy efficiency is maintained.
1:None
2:Protection
3:Protection / Economy
4:Protection / Economy / Pre-Comfort
ManOpLockCnf
3:Protection /
Economy
(d) CmfCndTrg
Configuration of trigger sent by AF for a change of room operating mode towards Comfort.
Protection/Economy/Pre-Comfort to Comfort
1:None
2:Energy efficiency condition
3:Comfort condition
PrtEcoPcfToCmf
3:Comfort
condition
Protection/Economy to Pre-Comfort
Enumeration see PrtEcoPcfToCmf
PrtEcoToPcf
1:None
Protection to Economy
Enumeration see PrtEcoPcfToCmf
PrtToEco
1:None
Repetition time energy efficiency trigger → Repeating
the trigger wipes out local manual commands (applies
to automatic trigger only).
RptTiEefTrg
60 [min]
Repetition number energy efficiency trigger (applies to
automatic trigger only)
RptNumEefTrg
0
(d) EefCndTrg
Configuration of trigger sent by AF for a change of room operating mode away from Comfort.
See note below.
Comfort/Pre-Comfort/Economy to Protection
1:None
2:Energy efficiency condition
3:Comfort condition
CmfPcfEcoToPrt
2:Energy efficiency
condition
Comfort/Pre-Comfort to Economy
Enumeration see CmfPcfEcoToPrt
CmfPcfToEco
2:Energy efficiency
condition
Comfort to Pre-Comfort
Enumeration see CmfPcfEcoToPrt
CmfToPcf
2:Energy efficiency
condition
Manual setpoint adjustment & EefCndTrg
The default configuration will reset a user-entered setpoint adjustment when the
room mode changes. To eliminate this reset, do the following:
- Set Comfort/Pre-Comfort to Economy (CmfPcfToEco) to "None"
- Set Comfort to Pre-Comfort (CmfToPcf) to "None"
These parameters are in the AF, Room operating mode determination
ROpModDtr. They are not BACnet objects, so ABT Site is required to access them.