Application

Application Notes
Sequence of Operation Summary
27
Siemens Industry, Inc.
A6V11692055
Smart Infrastructure Building Products
2019-04-01
CLG STPT EFF Present cooling setpoint (PrSpC)
RM TEMP STPT Room temperature setpoint (SpTR)
RM TEMP SHFT Room temperature setpoint shift (SpTRShft)
CMF CLG STPT Cooling setpoint for comfort (SpCCmf)
CMF HTG STPT Heating setpoint for comfort (SpHCmf)
STBY C DELTA Delta cooling setpoint for pre-comfort (DSpCPcf)
STBY H DELTA Delta heating setpoint for pre-comfort (DSpHPcf)
ECO CLG STPT Cooling setpoint for economy (SpCEco)
ECO HTG STPT Heating setpoint for economy (SpHEco)
PROT CLGSTPT Cooling setpoint for protection (SpCPrt)
PROT HTG SP Heating setpoint for protection (SpHPrt)
H.C STATE Heating/cooling state (HCSta)
Supply airflow setpoints
Min and max supply airflow heating and cooling setpoints, separately configurable:
HTG FLOW MIN Supply air VAV minimum air volume flow for heating
(VavSuAirFlMinH)
HTG FLOW MAX Supply air VAV maximum air volume flow for heating
(VavSuAirFlMaxH)
CLG FLOW MIN Supply air VAV minimum air volume flow for cooling
(VavSuAirFlMinC)
CLG FLOW MAX Supply air VAV maximum air volume flow for cooling
(VavSuAirFlMaxC)
Min and max supply airflow ventilation setpoints:
VENT FLO MIN Supply air VAV minimum air volume flow for ventilation
(VavSuAflMinVnt)
VENT FLO MAX Supply air VAV maximum air volume flow for ventilation
(VavSuAflMaxVnt)
Additional ventilation parameters, separately configurable per occupancy mode:
Room minimum ventilation flow setpoints