Application

Application Notes
Dual Duct Sequence Configurations
22
Siemens Industry, Inc.
A6V11692055
Smart Infrastructure Building Products
2019-04-01
Parameter configuration for use case 5a:
VavSuChovrCnd1 = Cooling
VavSuChovrCnd2 = Heating
VntDuctSprt = Both ducts
CtlStrgy = Mixing control
VntSprtDdband = Duct 1 (mixing will occur at/during setpoint for Duct 2 hot duct)
Minimum ventilation parameter(s)* = desired CV flow
*In the room AF for ventilation control (VavVntCtl) set min vent parameter for Comfort mode (AirFlMinRCmf) to
desired CV flow; the min vent setpoint object in VavSuDuald11 (VavSuAflMinVnt) can be set to zero when the
minimum ventilation parameters are used for min vent settings.
Note that if minimum ventilation parameter is not set high (for example during Economy mode) constant vol-
ume is not provided: