Application

Point Database
93
Siemens Industry, Inc.
A6V11692053
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Instan
ce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
19
CMF HTG
STPT
APrcVal
32
SpHCmf
Heating setpoint for
comfort
70
(21)
DEG F
(DEG
C)
--
--
--
20
PROT HTG SP
ACnfVal
33
SpHPrt
Heating setpoint for
protection
45
(7)
DEG F
(DEG
C)
--
--
--
21
ECO HTG STPT
ACnfVal
34
SpHEco
Heating setpoint for
economy
55
(12)
DEG F
(DEG
C)
--
--
--
22
STBY H DELTA
ACnfVal
35
DSpHPcf
Delta heating setpoint
for pre-comfort
2
(1)
DEG F
(DEG
K)
--
--
--
23
CMF H SP EFF
ACalcVal
36
PrSpHCmf
Present heating
setpoint for comfort
--
DEG F
(DEG
C)
--
--
--
24
STBY H SPEFF
ACalcVal
37
PrSpHPcf
Present heating
setpoint for pre-
comfort
--
DEG F
(DEG
C)
--
--
--
25
HTG STPT EFF
APrcVal
38
PrSpH
Present heating
setpoint
--
DEG F
(DEG
C)
--
--
--
26
ECO H SP EFF
ACalcVal
39
PrSpHEco
Present heating
setpoint for economy
--
DEG F
(DEG
C)
--
--
--
27
PROT H SPEFF
ACalcVal
40
PrSpHPrt
Present heating
setpoint for protection
--
DEG F
(DEG
C)
--
--
--
28
RM TEMP
STPT
APrcVal
41
SpTR
Room temperature
setpoint
--
DEG F
(DEG
C)
--
--
--
29
RM TEMP
SHFT
APrcVal
42
SpTRShft
Room temperature
setpoint shift
0
DEG F
(DEG
K)
--
--
--
30
ECO DCV STPT
ACnfVal
45
SpAQualREco
Setpoint room air
quality for economy
1500
ppm
--
--
--
31
PROT DCV SP
ACnfVal
46
SpAQualRPrt
Setpoint room air
quality for protection
2000
ppm
--
--
--
32
STBY DCV SP
ACnfVal
47
SpAQualRPcf
Setp.room air quality
for pre-comfort
1200
ppm
--
--
--
33
VENT SP EFF
APrcVal
48
PrSpVnt
Present ventilation
setpoint
--
ppm
--
--
--
34
CMF IAQ STPT
ACnfVal
49
SpAQualRCmf
Setpoint room air
quality for comfort
1000
ppm
--
--
--
35
RM DCV EVAL
ACalcVal
50
RAQual
Room air quality
--
ppm
--
--
--
36
RM TEMP
EVAL
ACalcVal
51
RTemp
Room temperature
--
DEG F
(DEG
C)
--
--
--
37
OA TEMP 1
APrcVal
52
TOa
Outside air
temperature
--
DEG F
(DEG
C)
--
--
--
38
OA HUM
APrcVal
53
HuRelOa
Relative outside
humidity
--
rh
--
--
--