Application
Point Database
82
Siemens Industry, Inc.
Application Note
A6V11692053
Smart Infrastructure – Building Products
2019-04-01
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Defaul
t
Value
Units
Enumeration
On
Text
Off
Text
91
RM OP MODE
MPrcVal
17
ROpMod
Room operating mode
Protec
t
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
92
GREEN LEAF
MPrcVal
19
REei
Energy efficiency
indication room
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
93
RM LGT
GRNLF
MCalcVa
l
20
RLgtEei
Room energy efficiency
ind.lighting
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
94
RM SHD
GRNLF
MCalcVa
l
21
RShdEei
Room energy efficiency
ind.shading
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
95
RMHVAC
GRNLF
MCalcVa
l
24
RHvacEei
Room energy efficiency
indication HVAC
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
96
H.C STATE
MCalcVa
l
25
HCSta
Heating/cooling state
Neithe
r
--
1:Neither
2:Heating
3:Cooling
--
--
97
NEXT OP
MODE
MPrcVal
26
NxROpMod
Next room operating
mode
Protec
t
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
98
PLANT
OPMODE
MPrcVal
27
PltOpMod
Plant operating mode
Off
--
1:Off
2:Protect
3:Economy
4:PrComfrt
5:Comfort
6:Warm-up
7:CoolDown
8:RmLTProt
9:NUsed1
10:FreeCool
11:NghtCool
12:Vent
13:NUsed2
14:AVlFlOf
15:SmCtPoPr
16:SmCtNgPr
17:Purge
--
--
99
DCV IND EVAL
MCalcVa
l
28
RAQualInd
Room air quality
indication
Undef
--
1:Undef
2:Poor
3:Okay
4:Good
--
--
100
HC DEMAND
MCalcVa
l
35
HCDmd
Heating/cooling demand
Neithe
r
--
1:Neither
2:Heating
3:Cooling
--
--