Data Sheet for Product

6
A6V10502844
2021-07-19
Inputs
Analog Inputs
Resistance sensor Temperature measurement Voltage measurement
AI 1000 Ω AI PT1K 375 (NA)*) AI 0 to 10V
AI 2500 Ω AI PT1K 385 (EU)*) AI 0 to 10V (0 to 100%)
AI 10 KΩ AI (LG-)Ni1000*)
AI 100 KΩ AI Ni1000 DIN*)
AI T1 (PTC)*)
AI NTC10K (Type II)**)
AI NTC100K**)
* A fixed value of 1 Ω is calibrated to correct line resistance.
** Configurable default.
Digital Inputs
Contact voltage Universal input: 18V
Digital input: 21V
Contact current Universal input: 1.2 mA; 7.4 mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ
Differential pressure sensor (inputs P1+, P1-)
Connections (nipple diameter) Dia. 5.2 mm (0.20 in)
Measuring range 0 to 500 Pa (0 - 2.01 in WC)
Overload range 0 to 100 kPa (0 - 402 in WC)
Measuring range accuracy
Zero point accuracy
Resolution
4.5%
0.2 Pa
12 bit