Data Sheet for Product

5
Siemens Industry, Inc.
A6V10502844
Smart Infrastructure
2021-07-19
Technical data
Housing
Color RAL 7035 (light-gray)
Dimensions 180 mm (7.09 in) x 104.5 mm (4.11 in) x 59.5 mm (2.34
in)
Weight
Packaging
ca. 340 g (11.99 oz)
ca. 40 g (1.41 oz)
Function data
Communication
A/D Resolution (analog in)
D/A Resolution (analog out)
14 Bits
12 Bits
Power data
Power supply
Operating voltage AC 24V -15%/+20%
Frequency 50/60 Hz
Internal fuse 4 A irreversible
Transformer with secondary current limitation of max. 10
A or external secondary current fuse
Non-renewable fuse
Circuit breakers
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN 60898
Apparent power (VA) for transformer design
Base Model Base load Max. load
Triac output
AC 24V~
0.25 A each
Max. load all
Aux. outputs
AC 24V~
Max. load
KNX PL-Link
(at 50 mA)
Max. load
DC 24V+ (2.4
W)
)
Max. Allowed
Power
consumption
including
connected field
devices
DXR2.E12P 8 6 x 6 = 36 12 4 - 60
NOTE:
To calculate the total VA, add the Base Load + the number of Triacs + field supplies+ KNX
PL-Link devices.
This cannot exceed the maximum power consumption. See the Wiring Guidelines for more