Application
Point Database
69
Siemens Industry, Inc.
Application Note
A6V11692042
Smart Infrastructure – Building Products
2019-04-01
14064 Point Database
The table shows US engineering units and values, and also CA engineering units
and values. CA values shown in parentheses ( ).
#
Descriptor
Object
Type
Insta
nce #
Desigo
Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
1
ROOM DCV 3
AI
56
AQualR
Room air quality
--
ppm
--
--
--
2
ROOM HUM 3
AI
57
HuRelR
Relative humidity for
room
--
rh
--
--
--
3
ROOM TEMP
21
AI
58
TR
Room temperature
--
DEG F
(DEG C)
--
--
--
4
SPLY TEMP 4
AI
110
TSu
Supply air temperature
--
DEG F
(DEG C)
--
--
--
5
SU DIFF 1P 3
AI
146
VavSuDiffP
1
Supply air VAV
differential pressure 1
--
in H2O
(Pa)
--
--
--
6
SU DIFF 2P 1
AI
147
VavSuDiffP
2
Supply air VAV
differential pressure 2
--
in H2O
(Pa)
--
--
--
7
HTG V POS 1
AO
25
HclVlvPos
Heating coil valve
position
--
PCT
--
--
--
8
1DMPR POS 3
AO
198
VavSuPos1
Supply air VAV position 1
--
PCT
--
--
--
9
2DMPR POS 3
AO
201
VavSuPos2
Supply air VAV position 2
--
PCT
--
--
--
10
APPLICATION
ACnfVal
4
AppNr
Application number
14064
--
--
--
--
11
CMF CLG
STPT
APrcVal
14
SpCCmf
Cooling setpoint for
comfort
75
(24)
DEG F
(DEG C)
--
--
--
12
STBY C DELTA
ACnfVal
15
DSpCPcf
Delta cooling setpoint for
pre-comfort
2
(1)
DEG F
(DEG K)
--
--
--
13
CLG STPT EFF
APrcVal
16
PrSpC
Present cooling setpoint
--
DEG F
(DEG C)
--
--
--
14
PROT
CLGSTPT
ACnfVal
17
SpCPrt
Cooling setpoint for
protection
104
(40)
DEG F
(DEG C)
--
--
--
15
ECO CLG STPT
ACnfVal
18
SpCEco
Cooling setpoint for
economy
85
(30)
DEG F
(DEG C)
--
--
--
16
STBY C SPEFF
ACalcVal
19
PrSpCPcf
Present cooling setpoint
for pre-comfort
--
DEG F
(DEG C)
--
--
--
17
CMF C SP EFF
ACalcVal
20
PrSpCCmf
Present cooling setpoint
for comfort
--
DEG F
(DEG C)
--
--
--
18
ECO C SP EFF
ACalcVal
21
PrSpCEco
Present cooling setpoint
for economy
--
DEG F
(DEG C)
--
--
--
19
PROT C SPEFF
ACalcVal
22
PrSpCPrt
Present cooling setpoint
for protection
--
DEG F
(DEG C)
--
--
--
20
CMF HTG
STPT
APrcVal
32
SpHCmf
Heating setpoint for
comfort
70
(21)
DEG F
(DEG C)
--
--
--
21
PROT HTG SP
ACnfVal
33
SpHPrt
Heating setpoint for
protection
45
(7)
DEG F
(DEG C)
--
--
--
22
ECO HTG STPT
ACnfVal
34
SpHEco
Heating setpoint for
economy
55
(12)
DEG F
(DEG C)
--
--
--
23
STBY H DELTA
ACnfVal
35
DSpHPcf
Delta heating setpoint
for pre-comfort
2
(1)
DEG F
(DEG K)
--
--
--