Commissioning Instructions

Supply Air Temperature Reset using Central Functions
Configuration
4
8 | 21
Restricted
A6V12006922
Description
BACnet Name
(Abbreviated Name)
Type
Comment
Default Value
Maximum Supply Air
Temperature
TSuMax
(TSU MAX)
ACnfVal
Maximum allowable
supply air temperature.
During Heating, the SAT
will not be reset above
this temperature.
89.6 °F (32 °C)
Start Value for Cooling
SttValC
(START CLG)
ACnfVal
Value at which Cooling
mode would begin if the
temperature was above
this point. Used as Max
SAT if the changeover is
Neutral.
75.2 °F (24 °C)
Start Value for Heating
SttValH
(START HTG)
ACnfVal
Value at which Heating
mode would begin if the
temperature was below
this point. Used as Min
SAT if the changeover is
Neutral.
71.6 °F (22 °C)
Minimum Supply Air
Temperature
TSuMin
(TSU MIN)
ACnfVal
Minimum allowable
supply air temperature.
During Cooling, the SAT
will not be reset below
this temperature.
60.8 °F (16 °C)