Commissioning Instructions
DXR Templates and Central Functions
2
A6V12006922
Restricted
5 | 21
2 DXR Templates and Central Functions
Templates from Hvac12 (VAV) and Hvac13 (FPB) DXR application types are used to configure Supply Air
Temperature Reset (SAT). These applications come with demand signals (from 0-100%) that can be used
in conjunction with AHU primary plant controllers to adjust the SAT setpoint. In addition, a Central Function
DXR can be used to bridge data easily between the zones and the AHU. The DXR template applications
and Central Function DXR together allow for efficient collection of room data for use in SAT Reset.
NOTICE! Title 24 Fault Detection for VAV and FPB Templates
For compliance with Title 24, a Fault Detection and Diagnostics (FDD) configured template should be used.