Commissioning Instructions
Central Functions
Configuring Central Function for Supply Air Temperature Setpoint Evaluation
5
A6V12006922
Restricted
15 | 21
5.4 Configuring Central Function for Supply Air Temperature
Setpoint Evaluation
1. Choose the Central HVAC Function.
2. Choose Supply chain for air.
3. Click the drop down, and change None to Supply chain air 11, for central AHU.
(Note that selections for Setpoint for supply air temp determ. and Changeover condition determ.for.air
are changed to active with that selection.)