Commissioning Instructions
19
Restricted
A6V12093876
Configuring Group Members and Masters
Group master/member communication is how all central functions read and write to
other applications. The high-level central function controls a single Group Master
object. This Master object is then what writes to the Group Member objects in the lower
level application functions. Because of this, it is extremely important to make sure to
set up the member/master connection for each central function, as otherwise there will
be no communication between the member and master, or the Central Function DXR
and the VAV Terminal DXR. It is also possible here to simply not select any
subordinate Automation Stations that are not involved with this central function
application.
1. Select the Building component.
2. Select the Add device button and add the Central Function to the building
structure.
3. Select the Central Functions task.
4. Add a Central Function hierarchy. Expand the Unplaced central functions
hierarchy to expose the SplyAirMst Group Master.
5. Drag the unplaced Central function to the Hierarchy element