Commissioning Instructions

Restricted
A6V12093876
Central Operating Mode Extended Function
(CenOpModExtd11)
This AF is used ONLY for presence mode and operating strategy. CenOpModExd11
permits detailed central operation of presence mode for HVAC, lighting and shading
as well as operating strategy for lighting and shading. The AF distributes these
commands either to subordinate AFs or directly to the connected rooms.
Note, CenOpModExtd11 is used only with outside logic or scheduling. Without ex-
ternal logic, these points will not command any objects or change any operating
modes at the room level.
IMPORTANT: Use ONLY when different presence operating modes are required within the same room operating
mode. For example, from 6pm to 8pm, lighting presence mode in Economy can be “Consider present & absent”
and then from 8pm to 7am it can be “Consider absent”. Using this method will override the local operating mode
concept, as it commands at Priority 14 within the room.
, Point Database
Description
BACnet Name
(Abbreviated name)
Type
HVAC Presence Mode
HvacPscMod
MPrcVal
Lighting Presence Mode
LgtPscMod
MPrcVal
Shading Presence Mode
ShdPscMod
MPrcVal
Lighting Operating Strategy
LgtOpStrgy
MPrcVal
Shading Operating Strategy
ShdOpStrgy
MPrcVal