Commissioning Instructions
10
Restricted
A6V12093876
Point Database
Description
BACnet Name
(Abbreviated)
Type
Direction of Data Flow
From
To
Operating mode switch
OpModSwi
BI
External contact
(switch or clock)
Commands CenOpModCmdV to
Comfort @ Prio16: Auto mode 7,
and sends the value to CenOssc11
Central operating mode
command value
CenOpModCmdv
MPrcVal
From Scheduler or
DesigoCC manual
operator commands
Scheduler commands @ Prio15:
Auto mode 6.
Desigo CC commands @
8:Man. operating mode 2 or 13:Man
mode 3.
Value sent to CenOssc11
CoolDwn (signal from
scheduler)
Cooldwn
BCnfVal*
From scheduler
Cool-Down value (from
superordinate AF)
CoolDwnVal
BCalcVal
From superordinate
CenOpMod11 AF
Free cooling reqeust
(signal from scheduler)
FreeCReq
BCnfVal*
From scheduler
Free cooling request value
(from superordinate AF)
FreeCReqVal
BCalcVal
From superordinate
CenOpMod11 AF
Warm-Up (signal from
scheduler)
WarmUp
BCnfVal*
From scheduler
Warm-Up value (from
superordinate AF)
WarmUpVal
BCalcVal
From superordinate
CenOpMod11 AF
Night cooling request
NgtCReq
BCnfVal*
From scheduler
Night cooling request value
(from superordinate AF)
NgtCReqVal
BCalcVal
From superordinate
CenOpMod11 AF
Next Operating Mode
NxOpMod
MCnfVal*
From Scheduler
Next Operating Mode Value
(from superordinate AF)
NxOpModVal
MCalcVal
From superordinate
CenOpMod11 AF
Room climate operating
mode input value
RClmOpModIn
MCalcVal
Calculated value for operating
mode to the room. Either uses
current ROpMod or if any of the
above modes are active can send
those.
*No configuration is required in ABT Site default values (BACnet objects are used only as interface).