Assortment / System Description

Room coordination functions
Room functions: Room coordination
13
A6V10866237_en--_b_08 59 | 275
Room control by switching the operating mode
The room operating mode can automatically control the various applications for
HVAC, lighting, or shading. Two trigger signals are available in each room. They
are sent to all disciplines on a configured change to room operating mode
occurs. The two triggers are "Energy efficiency condition" and "Comfort
condition".
You can determine which trigger to send to the disciplines for each change in
operating mode.
Description Name Default value
Comfort/Pre-Comfort/Economy to Protection
1:None
2:Energy efficiency condition
3:Comfort condition
CmfPcfEcoToPrt 2:Energy
efficiency
condition
Comfort/Pre-Comfort to Economy
Enumeration see CmfPcfEcoToPrt
CmfPcfToEco 2:Energy
efficiency
condition
Comfort to Pre-Comfort
Enumeration see CmfPcfEcoToPrt
CmfToPcf 2:Energy
efficiency
condition
Protection/Economy/Pre-Comfort to Comfort
Enumeration see CmfPcfEcoToPrt
PrtEcoPcfToCmf 3:Comfort
condition
Protection/Economy to Pre-Comfort
Enumeration see CmfPcfEcoToPrt
PrtEcoToPcf 1:None
Protection to Economy
Enumeration see CmfPcfEcoToPrt
PrtToEco 1:None
The "Energy efficiency condition" trigger can be repeated automatically. The
number of repeats to the disciplines as well as the time between repetitions
can be configured.
Description Name Default value
Repeat time energy efficiency trigger;
A repeat of the trigger overrides local, manual
commands. The parameter affects only the
automatic trigger
RptTiEefTrg 60 min
Number of repetitions energy efficiency trigger; The
parameter affects only the automatic trigger
RptNumEefTrg 0
Trigger signals indicate
switch to energy
efficiency or Comfort
Repeat trigger