Assortment / System Description

Control function
Room controller and setpoints
11
A6V10866237_en--_b_08 39 | 275
11.4.8 Controller operating mode for heating and cooling
aggregates based on the plant operating mode
For the room operating modes, the controller operating mode can be configured
on DXR2 for all heating and cooling aggregates.
Description Name Default value
Cooling coils in Comfort
0:Modulating
1:2-position
CoilCmf 0:Modulating
Coil coils in Pre-Comfort CoilPcf 0:Modulating
Coiling coils in Economy CoilEco 0:Modulating
Cooling coils in Protection CoilPrt 0:Modulating
Coiling coils in cool down CoilCoolDn 0:Modulating
Chilled ceiling in Comfort RadDevCmf 0:Modulating
Chilled ceiling in Pre-Comfort RadDevPcf 0:Modulating
Chilled ceiling in Economy RadDevEco 0:Modulating
Chilled ceiling in Protection RadDevPrt 0:Modulating
Chilled ceiling in cool down RadDevCoolDn 0:Modulating
Heating coils in Comfort CoilCmf 0:Modulating
Heating coils in Pre-Comfort CoilPcf 0:Modulating
Heating coils in Economy CoilEco 0:Modulating
Heating coils in Protection CoilPrt 0:Modulating
Heating coils in warm up CoilWarmUp 0:Modulating
Radiator & heated ceiling in Comfort RadDevCmf 0:Modulating
Radiator & heated ceiling in Pre-Comfort RadDevPcf 0:Modulating
Radiator & heated ceiling in Economy RadDevEco 0:Modulating
Radiator & heated ceiling in Protection RadDevPrt 0:Modulating
Radiator & heated ceiling in warm up RadDevWarmUp 0:Modulating
The controller operating mode modulating controls based on one PID controller
(amplification, integral time, etc.).
Controller operating
mode modulating