Assortment / System Description

Lighting applications
Constant lighting control with one light group in the room
22
A6V10866237_en--_b_08 225 | 275
The DXR2 can control KNX PL-Link push buttons or room operator units with
integrated LED state displays. The following state displays can be configured:
Always off:
State LEDs are always switched off on push buttons/room operator unit.
Lighting on:
The state LEDs for the push buttons (switch off/darker) are switched on if
the lights are switched on.
Lighting off:
The state LEDs for the push buttons (switch on/brighter) are switched on if
the lights are switched off.
Manual operation lock:
All state LEDs are switched on if the push buttons/room operator unit is
locked for manual operation.
Lighting on, or manual operation lock:
The state LEDs of the push buttons (switch off/darker) are switched on if
the lights are switched on and all state LEDs are switched on if manual
operation is locked.
Lighting off, or manual operation lock:
The state LEDs of the push buttons (switch on/brighter) are switched on if
the lights are switched off and all state LEDs are switched on if manual
operation is locked.
Description Name Default value
Room operator unit, LED indication RuLED Lighting off, or
manual operation
lock
22.5 Constant lighting control with one light group
in the room
The constant lighting control application ensures seamless control of artificial
light based on room brightness. A brightness sensor mounted on the ceiling in a
room acquires the brightness in the room as a sum total of artificial light and
daylight. The previously defined brightness value in the room is maintained at a
constant level. Artificial light is switched off if not needed.
Control of state LED