Data Sheet for Product
Table Of Contents
7
Siemens Industry, Inc.
A6V11339446
Smart Infrastructure
2021-07-19
Wiring connections
Pluggable screw terminals Copper wire or copper stranded wire with connector
sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1 mm
2
(22 to 18 AWG)
Copper stranded wire without connector sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1.5 mm
2
(22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Slotted screws Size 1, tightening torque 0.6 Nm (0.44 lb-ft)
Wiring lengths for signals KNX PL-Link 80 m (260 ft) with internal bus power or
300 m (990 ft) with external power supply
Ethernet 100 m (330 ft)
Signal lines 80 m (260 ft)
For inputs AI 100 kOhm, AI NTC10K, AI NTC100K: 30 m
(100 ft) or 80 m (260 ft), if shielded.
KNX/PL-Link Network and Power Wriring.*
Cable configuration 1 or 2 twisted pair
- Pair 1 red/black
- Pair 2 yellow/white
Gauge 20 AWG (solid copper)
Twists per foot 4 Minimum
Capacitance 30 pF/foot or less
Shields 100% foil with drain wire
UL type 300Vrms, CMP (75 °C or higher)
CSA type 300Vrms, FT6 (75 °C or higher)
* Alternative 18 AWG STP CMP (Belden 6320FE 8771000)
Conformity
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
Observe national provisions and comply with the appropriate safety regulations.
Ambient conditions and protection classification
Climatic ambient conditions
● Transport and Storage
● Operation
● Temperature -25 to 70°C (-13 to 158°F)
Air humidity 5 to 95% rh.
● Temperature -5 to 45°C (23 to 113°F)/
-5 to 50 °C (23 to 122°F)
Air humidity 5 to 95% rh.