Data Sheet for Product
Table Of Contents
6
Siemens Industry, Inc.
A6V11339446
Smart Infrastructure
2021-07-19
Digital Inputs
Contact voltage Universal input: 18V
Digital input: 21V
Contact current Universal input: 1.2 mA; 7.4 mA initial current
Digital input: 1.6 mA; 9.4 mA initial current
Contact resistance for closed contacts Max. 100 Ω
Contact resistance for open contacts Min. 50 kΩ
Differential pressure sensor (inputs P1+, P1-)
Connections (nipple diameter) Dia. 5.2 mm (0.20 in)
Measuring range 0 to 500 Pa (0 - 2.01 in WC)
Overload range 0 to 100 kPa (0 - 402 in WC)
Measuring range accuracy
Zero point accuracy
Resolution
4.5%
0.2 Pa
12 bit
Outputs
Analog Outputs
AO 0-10 V Max. 1 mA
Switching outputs Triac (outputs Y3...Y6)
Type High side
The Triac closes the contact to AC 24 V
Switching voltage AC 24 V
Permissible load 500 mA / 12 VA per output
Protection Short-circuit proof
Connections
Interfaces
Ethernet Plugs: 2 x RJ45, screened
Interface type: 10Base-T/100BASE-TX, IEEE 802.3
compatible
Bitrates: 10/100 Mbps, autosensing
Protocol: BACnet over UDP/IP
USB (2.0) Plug: Type B
Data rate: 12 Mbps
KNX Type: KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Bus power: 50 mA
Short-circuit proof Protection against faulty wiring at max.
AC 24 V