Commissioning Instructions

Step 8 Fault detection and diagnostics parameters
26
Supply position change time limit 1
The oscillation counter will be reset, if
the position tolerance has not been
exceeded for this length of time.
ACnfVal
600
s
(SuPosChgTiLim1)
Supply position change time limit 2
The oscillation counter will be reset, if
the position tolerance has not been
exceeded for this length of time.*
ACnfVal
600
s
(SuPosChgTiLim2)
* For example, if 4 oscillations occur, but a fifth oscillation is not detected before 600 seconds elapse, then the counter is
reset to 0.