Commissioning Instructions
Step 8 – Fault detection and diagnostics parameters
21
Unrestricted
A6V12035398
Supply heat temp fault determination
IF
AND
THEN
Supply air Temperature <
Supply air Setpoint minus
temp threshold
Supply air temperature >
Max (Supply air Setpoint,
Primary air Temp) plus
temp threshold
conditions exists for
greater than fault delay
Supply temp
FAULT
AHU MODE = ON
and
Supply Air flow
setpoint > flow
threshold
NO
-
-
Normal
YES
-
YES
Lo Temp
-
NO
-
Normal
-
YES
YES
Hi Temp
AHU MODE = OFF
or
Supply Air flow
setpoint < flow
threshold
-
-
-
Normal
• For FDD Fault determinations to be enabled, the following conditions must be met.
• DXR object ‘AHU MODE’ (set by central commands) present value is ‘On’ (1)
• See note in Step 9 when AHU MODE is overridden for testing.
• One (or both) of the Supply air flow setpoint 1 (2) must be greater than configuration
parameter ‘Enable VAV flow setpoint’.
• Supply air temperature fault: Hi temp
▪ IF Primary air Temperature is not being updated (e.g. 0C, 32F)
• Fault: Supply air temperature remains greater than Supply air temperature setpoint by the
differential Supply air heating temperature fault tolerance for the duration of Supply air
heating temp fault delay (default 600 seconds).
• Normal: When the supply temperature and the supply temperature setpoint returns to be
within the fault tolerance, the fault will be reset automatically.
▪ IF Primary air Temperature is updated by the central functions or field panel:
• Fault: Supply air temperature remains greater than
The larger of Supply air temperature setpoint and Primary air temperature by the
differential Supply air heating temperature fault tolerance for the duration of Supply air
heating temp fault delay (default 600 seconds).
• Normal: When the supply temperature and the larger of supply temperature setpoint and
Primary air temperature returns to be within the fault tolerance, the fault will be reset
automatically.
• Supply air temperature fault: Low temp
▪ Fault: Supply air temperature remains less than Supply air temperature setpoint by the differential
Supply air heating temperature fault tolerance for the duration of Supply air heating temp fault delay
(default 600 seconds).
• Normal: When the supply temperature and the supply temperature setpoint return to be within the
fault tolerance, the fault will be reset automatically.